Impulse Noise - DTX CableAnalyzer

The test takes noise voltage samples every second on pair 3,6. The user can change the threshold from 10 mV to 500 mV.
 
참고:
To extend battery life, connect the ac adapter when monitoring impulse noise for extended periods. The testers power down timer is disabled during the impulse noise test.
 
Monitoring impulse noise without a smart remote may produce unreliable test results.
 
To monitor impulse noise: 
  
    1. Attach twisted pair link interface adapters to the tester and smart remote. 

    2. Turn the rotary dial to MONITOR and turn on the smart remote; then connect to the testers to the ends of the cabling. 

    3. Press Test Button

    4. To adjust the noise threshold, press F3 Buttonto Stop; then use the Up Arrow Keyand Down Arrow Keykeys to change the value. Press Test Buttonto resume testing.
 
팁: Fluke Networks recommends a noise threshold of 30 mV with an average pulse rate below 0.01/sec for testing 1000BASE-T (Gigabit Ethernet) cabling.

To stop the test at any time, press Exit Button
  
            Impulse Noise Testing
 
참고:
If you disconnect the tester and smart remote during the impulse noise test, it takes several minutes for the remote to stop testing.