SC/APC to SC/APC duplex fiber loss testing with OptiFiber and DTX-SFM/SFM2 adapters
This article will guide you through the setup process for making an optical loss measurement on an SC/APC to SC/APC duplex link using the OptiFiber Modules OFTM-5632/OFTM-5732 along with a DTX-SFM/DTX-SFM2 adapter.
IMPORTANT RULES:
IMPORTANT RULES:
- Never insert an SC/APC connector into the OUTPUT PORT.
- You can insert an SC/APC connector into the INPUT PORT.
Before you start, clean AND INSPECT all end faces of your test reference cords using a fiberscope. Failure to do so will result in erratic readings. You should inspect and clean the test reference cords every 24 to 48 tests and reset the reference if needed. 왜 그렇습니까? You can pick up debris from the connectors you are testing. You can easily become a victim of cross contamination where you damage the connectors you are testing and your test reference cords.
- Press the SETUP key and go to the Loss/Length tab:
- Select the standard you wish to test against, in this example TIA-568-C Singlemode ISP. Make sure the TEST METHOD is set to 1 Jumper and the Connector Type to SC. This will ensure the help screens provide the correct information if needed.
- The NUMBER OF ADAPTERS is the number of mated connections added after you set the reference per fiber strand. Using this 1 Jumper method, a fiber link consisting of a patch panel connected to a patch panel would have an adapter count of 2.
- If you have verified the quality of your test reference cords, you can begin setting a reference.
- 중요: Always replace the caps on the fiber connectors whenever they are not inserted into the OptiFiber or DTX Smart Remote. This will prevent dust/dirt adhering to the end faces resulting in sporadic/negative loss readings
- Connect Duplex 1 as shown below: (Insert SC/UPC into the OptiFiber OUTPUT port and never remove it)
- Connect Duplex 2 as shown below: (Insert SC/UPC into the DTX Smart Remote OUTPUT port and never remove it)
- Press the FUNCTIONS key on the OptiFiber and highlight Set Loss/Length Reference.
- Press the ENTER key:
- Press the TEST key to set the reference, when complete you should see something similar to this:
With the DTX-SFM2, you should expect to see a value better than -8.00 dBm.
참고: -6.00 dBm is better than -8.00 dBm
Values within these ranges do not guarantee your test reference cords are clean. You must continually inspect and clean your test reference cords to avoid negative loss readings.
- You can enter the length of your test cords here for documentation purposes. Otherwise, press the F3 key OK.
- Remove the SC/APC plug from the INPUT port on the OptiFiber:
- Remove the SC/APC plug from the INPUT port on the DTX Smart Remote:
- Connect the SC/APC plug from Duplex 1 to the INPUT port of the OptiFiber:
- Connect the SC/APC plug from Duplex 2 to the INPUT port on the DTX Smart Remote:
- You are now ready to connect to your link to test.
- Connect the DTX Smart Remote with Duplex 2 to End 2 of your fiber link:
- Connect the OptiFiber with Duplex 1 to End 1 of your fiber link:
- Press the FUNCTIONS key.
- Highlight Loss/Length and press the ENTER key.